Viessmann Boiler Fault Codes: Vitodens Fault Finding
- ⭐ Trustpilot 4.6 Excellent, over 650 reviews
- Gas Safe registered: 973154
- Price match on like-for-like quotes
Quick answer
Viessmann Vitodens boilers show a fault code on the display. F4 means no flame signal was detected, so the burner did not light. F2 means the temperature limiter has responded, which relates to overheating or low water. Check gas and pressure, reset once, and call a Gas Safe engineer if it returns.
Contents
- 1 How Viessmann fault codes work
- 2 Viessmann Vitodens fault code table
- 3 F4: no flame signal
- 4 F2: temperature limiter has responded
- 5 Checking pressure on a Viessmann boiler
- 6 When to call a Gas Safe engineer
- 7 Is it time to replace a Viessmann?
- 8 Time for a new boiler?
- 9 Frequently asked questions
- 10 Related Eco Happy guides
How Viessmann fault codes work
Viessmann Vitodens boilers display a flashing fault code and the boiler either stops the burner or runs in a reduced mode. In Viessmann’s documentation, some faults are “burner in a fault state”, where the boiler needs a manual reset before the burner will run again, and others are “burner blocked”, where the burner resumes by itself if the cause is corrected.
An important caveat: codes and meanings differ between Vitodens models and markets. The table below uses Viessmann’s UK installation and service instructions for the Vitodens 100-W (types B1HC and B1KC). Other Vitodens models may use different lists: the newer Vitodens 050-W (types B0HA and B0KA), for example, shows numbered codes rather than F codes. Always check the user or installation guide for your own boiler, and Viessmann’s UK fault code page, before relying on any table.
When you contact an engineer, tell them the exact code as it appears, the model name on the front of the boiler, whether the burner lit at all, and whether the fault appeared after the heating had been off for a while. A boiler that fails on a cold start points toward ignition or condensate problems, while one that fails after running for a time points toward flow, temperature or sensor issues. That one detail can save a wasted visit.
Viessmann Vitodens fault code table
| Code | Boiler status | Meaning (Viessmann service instructions) |
|---|---|---|
| F1 | Burner in a fault state | Maximum flue gas temperature exceeded |
| F2 | Burner in a fault state | Temperature limiter has responded (overheat) |
| F3 | Burner in a fault state | Flame signal is already present at burner start |
| F4 | Burner in a fault state | There is no flame signal |
| F8 | Burner in a fault state | Fuel valve closes too late |
| F9 | Burner in a fault state | Fan speed too low during burner start |
| FA | Burner in a fault state | Fan idle state not reached |
| FC | Burner blocked | Electrical fan control (control unit) faulty |
| Fd | Burner blocked | Burner control unit fault |
Viessmann’s UK fault code checker also lists A4, an air lock in the internal circulation pump or minimum flow not achieved (on the Vitodens 222-F), and OC, insufficient power supply (on the Vitodens 100-W).
F4: no flame signal
Viessmann’s service table says F4 means no flame signal is present at the burner, and lists engineer checks of the ignition/ionisation electrode and its cable, gas pressure, gas train, ignition module and the condensate drain. In plain terms, the boiler tried to light and did not detect a flame.
What you can safely check: other gas appliances, prepayment credit, the gas tap, and whether the condensate pipe is frozen in cold weather (thaw only with warm, not boiling, water, at ground level). Then reset once using the method in your user guide. Everything else on that list is engineer work. See our existing page on Viessmann F4.
F2: temperature limiter has responded
F2 means the temperature limiter has responded, which is an overheat protection. The service table says to check the heating system fill level and the circulation pump, vent the system, and check the temperature limiter and its connecting leads. That points to low pressure, air or a circulation problem.
Check the pressure gauge and top the system up if it is low. Do not repeatedly reset. If F2 repeats, a pump, air lock or sensor issue is likely and needs a Gas Safe engineer.
Checking pressure on a Viessmann boiler
Several Viessmann codes are made worse by low pressure or air. Check your gauge when the system is cold and follow the pressure shown in your own manual, then use the filling loop to top up slowly. Our repressurising guide explains the general method. If you have to top up often, see boilers losing pressure.
Gas Safe warning
Do not open the boiler casing or touch gas, flue or other internal parts. Anything inside the boiler, including gas valves, burners, electrodes, fans, heat exchangers and circuit boards, must be dealt with by a Gas Safe registered engineer. If you smell gas, suspect a gas leak or flue fumes, or a carbon monoxide alarm sounds: turn off the gas at the meter if it is safe to do so, open doors and windows, do not use light switches or anything electrical, leave the property and call the National Gas Emergency Service on 0800 111 999.
When to call a Gas Safe engineer
- The code returns after one reset.
- Any code about the flame, fan or blower, gas valve, control unit or flue temperature.
- A burner that keeps going into fault mode.
- You smell gas or a carbon monoxide alarm sounds.
If your boiler is under Viessmann warranty, make sure repairs are done in line with the warranty terms and that annual servicing is up to date. Our Viessmann boiler guide has more on the brand and its models.
Is it time to replace a Viessmann?
Viessmann boilers have a good reputation, and we fit them. A recent Vitodens that is well serviced is usually worth repairing. An older one with a recurring failure may not be. If you are weighing it up, read our Vitodens 100-W guide and when a boiler is beyond repair.
Time for a new boiler?
If your Viessmann is old and keeps faulting, comparing a repair quote with a new boiler price can save money. Eco Happy fits new combi boilers from £1,928.99 fully fitted including VAT, with a Gas Safe registered engineer, the old boiler removed and a fixed price you can see online before you commit. Get my fixed boiler price in about a minute, or call 0114 387 7066. Boiler finance is available through a panel of lenders at 11.9% APR representative, subject to status (see boiler finance). Rated 4.6 Excellent, over 650 reviews on Trustpilot.
Frequently asked questions
What does F4 mean on a Viessmann boiler?
No flame signal is present. The burner did not light or the flame was not detected. Check gas supply and condensate pipe, then reset once and call an engineer if it returns.
What does F2 mean on a Viessmann boiler?
The temperature limiter, an overheat protection, has responded. Check water level and circulation, and have an engineer inspect it if it repeats.
How do I reset a Viessmann boiler?
Use the reset method in your user guide for your model. Reset once only. If the fault returns, call a Gas Safe engineer.
Are Viessmann fault codes the same on all models?
No. Codes and meanings vary by model and market. Check your own manual.
Is a Viessmann fault code dangerous?
Faults are safety shutdowns, not hazards in themselves. If you smell gas or a carbon monoxide alarm sounds, leave the property and call the National Gas Emergency Service.
Should I replace a Viessmann boiler with a fault?
Not necessarily. A recent boiler is often worth repairing. An older one with repeated faults may be better replaced.
Related Eco Happy guides
- Viessmann boilers
- Viessmann F4
- Viessmann Vitodens 100-W
- How to repressurise a boiler
- Boiler lockout
- Eco Happy boiler advice hub
Eco Happy Installs Limited (FRN 1051640) is a credit broker working with a panel of lenders. We are authorised and regulated by the Financial Conduct Authority as a credit broker, not a lender. The availability of finance and the terms offered will depend on your individual circumstances. Credit is subject to status, affordability and lender approval. Terms and conditions apply.